Al011 код ошибки delta

Artsen

Сообщения: 3
Зарегистрирован: 18 ноя 2015, 22:31

Сервопривод ASD-A2 Ошибка AL011

Здравствуйте коллеги.
Вопрос простой и прозаичный, важный для меня. Привод Asd-A2, периодически возникает ошибка AL011 (неисправность энкодера, следует проверить подключение цепей с обоих сторон, возможно следует заменить сервопривод).
Вопрос, может ли подобная ошибка возникать из-за механических повреждений оптической системы или данная ошибка возникает только при несправностях по электрической части энкодера или сервопреобразователя?
Спасибо



<= See All alarms of Delta servo

Name Description ALM WRN SRV ON Clear
Way

AL.011

Encoder Error

The encoder produces abnormal pulse   No re-power on
Causes Checking Method Actions
Wrong wiring of the encoder Check if the wiring follows the suggested wiring of the user manual. Correct wiring
The encoder is loose Check the drive connector of CN2 and encoder Install the encoder again
Bad connection of the encoder Check if the connection between CN2 of the drive and the encoder of the servo motor is loose Reconnect the wiring
The encoder is damaged Check if the motor is damaged Change the motor
     

(The above information is referenced from Delta Electronics IMSBU)

See ALL Alarms <=        ↓ The following content is contributed by users ↓

Other reasons Checking Method Actions
     
     

Sharing is a virtue. Please add the inadequacies of this article to benefit the public —

 
Ошибка AL001 (error AL001, AL1) — перегрузка по току;
Ошибка AL002 (error AL002, AL2) — перенапряжение;
Ошибка AL003 (error AL003, AL3) — пониженное напряжение;
Ошибка AL004 (error AL004, AL4) — подключен несовместимый двигатель;
Ошибка AL005 (error AL005, AL5) — ошибка функции Regeneration;
Ошибка AL006 (error AL006, AL6) — перегрузка;
Ошибка AL007 (error AL007, AL7) — превышение скорости;
Ошибка AL008 (error AL008, AL8) — несовместимый уровень входного импульсного сигнала;
Ошибка AL009 (error AL009, AL9) — выход за пределы заданного диапазона возможной позиции;
Ошибка AL011 (error AL011, AL11) — ошибка энкодера;
Ошибка AL012 (error AL012, AL12) — ошибка параметров настройки;
Ошибка AL013 (error AL013, AL13) — аварийная остановка;
Ошибка AL014 (error AL014, AL14) — достигнуто ограничение реверсивного движения;
Ошибка AL015 (error AL015, AL15) — достигнуто ограничение прямого(нереверсивного) движения;
Ошибка AL016 (error AL016, AL16) — перегрев IGBT транзисторов;
Ошибка AL017 (error AL017, AL17) — ошибка памяти EEPROM;
Ошибка AL018 (error AL018, AL18) — несовместимый сигнал энкодера;
Ошибка AL019 (error AL019, AL19) — ошибка связи RS-232, RS-485;
Ошибка AL020 (error AL020, AL20) — таймаут соединения RS-232, RS-485;
Ошибка AL022 (error AL022, AL22) — обрыв фазы на входе сервопривода;
Ошибка AL023 (error AL023, AL23) — предупреждение о перегрузке;
Ошибка AL024 (error AL024, AL24) — ошибка энкодера;
Ошибка AL025 (error AL025, AL25) — ошибка внутренней памяти энкодера;
Ошибка AL026 (error AL026, AL26) — ошибка энкодера повторилась 3 раза;
Ошибка AL027 (error AL027, AL27) — внутренняя ошибка энкодера;
Ошибка AL028 (error AL028, AL28) — ошибка сигнала энкодера;
Ошибка AL029 (error AL029, AL29) — ошибка сигнала абсолютной позиции;
Ошибка AL030 (error AL030, AL30) — неисправность двигателя;
Ошибка AL031 (error AL031, AL31) — неправвильная схема подключения;
Ошибка AL034 (error AL034, AL34) — ошибка связи с энкодером;
Ошибка AL035 (error AL035, AL35) — перегрев энкодера;
Ошибка AL040 (error AL040, AL40) — нестабильный сигнал позиции;
Ошибка AL041 (error AL041, AL41) — обрыв энкодера;
Ошибка AL042 (error AL042, AL42) — ошибка аналогового входного сигнала;
Ошибка AL044 (error AL044, AL44) — предупреждение о перегрузке;
Ошибка AL045 (error AL045, AL45) — неправильная настройка коэффициентов E-gear ratio;
Ошибка AL060 (error AL060, AL60) — потеряна абсолютная позиция;
Ошибка AL061 (error AL061, AL61) — пониженное напряжение питания энкодера;
Ошибка AL062 (error AL062, AL62) — код энкодера вне заданного предела;
Ошибка AL067 (error AL067, AL67) — перегрев энкодера;
Ошибка AL068 (error AL068, AL68) — ошибка считывания абсолютной позиции;
Ошибка AL069 (error AL069, AL69) — подключен несовместимый тип двигателя;
Ошибка AL06A (error AL06A, AL6A) — абсолютные координаты не инициализированы;
Ошибка AL070 (error AL070, AL70) — энкодер не завершил выполнение команды сервопривода;
Ошибка AL083 (error AL083, AL83) — перегрузка сервопривода;
Ошибка AL085 (error AL085, AL85) — абсолютные координаты не инициализированы;
Ошибка AL095 (error AL095, AL95) — не подключен внешний тормозной резистор;
Ошибка AL099 (error AL099, AL99) — еобходим сброс после обновления прошивки DSP.

Обсудить на форуме

ASDA-A2

AL008:Abnormal Pulse Command

Causes

The pulse command

frequency is higher than

the rated input

frequency.

AL009:Excessive Deviation of Position Command

Causes

Parameter P2-35 is set

too small

The setting of the gain

value is too small.

The torque limit is too

low.

Excessive external load

Improper setting of E-

gear ratio

AL011:Encoder Error

Causes

Wrong wiring of the

encoder

The encoder is loose

Bad connection of the

encoder

The encoder is damaged Check if the motor is damaged

AL012:Adjustment Error

Causes

The analog input contact

is incorrectly set back to

zero

The detection device is

damaged

AL013:Emergency Stop

Causes

Press the emergency

stop button

10-12

Checking Method

Use the scope to check if the input

frequency is over the rated input

frequency.

Checking Method

Check the setting value of

parameter P2-35 (The warning

condition of excessive position

deviation)

Check if the setting value is

appropriate

Check the torque limit value

Check the external load

Make sure if the proportion of P1-44

and P1-45 is appropriate.

Checking Method

Check if the wiring follows the

suggested wiring of the user

manual.

Check the drive connector of CN2

and encoder

Check if the connection between

CN2 of the drive and the encoder of

the servo motor is loose

Checking Method

Measure if the voltage of the analog

input contact is the same as the

ground voltage

Reset the power supply

Checking Method

Check if the emergency stop button

is enabled.

Chapter 10 Troubleshooting

Corrective Actions

Correctly set the input pulse

frequency.

Corrective Actions

Increase the setting value of P2-35

(The warning condition of

excessive position deviation)

Correctly adjust the gain value

Correctly adjust the torque limit

value

Reduce the external load or

evaluate the motor capacity again

Correctly setup E-gear ratio

Corrective Actions

Correct wiring

Install the encoder again

Reconnect the wiring

Change the motor

Corrective Actions

Correctly ground the analog input

contact

If the error still occurs after reset,

send the drive back to the

distributors or contact with Delta.

Corrective Actions

Activate emergency stop

Revision February, 2017

В 28.08.2021 в 09:33, sva73 сказал:

Странно, что у этой фирмы из Краснодара поставляющей длительное время мойки с Китая, нет специалистов в этой области.

В Краснодаре они точно есть, но вероятно вызывать специалистов из Краснодара владельцу автомойки было накладно, учитывая что территориально мы находимся в СКФО.

В итоге, как мне сказали, мойка простаивала 4 дня, за это время успели пригласить двух/трёх электриков, которые запороли им всю проводку))) Ну а потом как-то вышли на меня…

В 28.08.2021 в 09:32, sva73 сказал:

Если вы смогли определить причину поломки связанную с серводвигателем, то значит вы специалист и что то умеете. Вы где то работаете или работали ранее по схожему направлению.

На досуге занимаюсь ремонтом всякой электроники (мониторы, телевизоры, материнские платы, блоки питания, стабилизаторы и т.д. и т.п.). Хобби.

За выездные работы берусь крааайне редко. Из того что помню это: ремонт паечного станка для пластиковых окон,  ремонт светодиодного рекламного LED экрана, ремонт 3D-принтера в школе, восстановление сушильной камеры 30 куб.м. для сушки древесины. И вот сейчас столкнулся с робот-мойкой.

В 28.08.2021 в 09:32, sva73 сказал:

У вас была заработная плата соответствующего специалиста.  Вы потратили определенное время на устранение неполадки. Вы можете привязаться к своей З.П. и времени накинуть коэффициент на то, что это делали вы (коэффициент сугубо личный) + поездки и бензин.

Там где я работаю зарплата у меня копеечная и к ней привязываться точно не стоит)) 

В общем по времени ушло примерно 9-10 часов: поиск и изучение документации на оборудование, прозвонка, демонтаж привода, всяческие поездки, капризы владельца мойки, монтаж привода…

Самое обидное то, что почти половина этого времени была потрачена на капризы хозяина мойки, связанные с фотосессиями и видеосъемкой процесса работы, постоянными телефонными звонками, поисками мегомметра, дополнительной поездкой к мастеру по перемотке двигателей, ненужной разборкой/сборкой привода и т.п.

Узнавал насчёт цен за работу, мне сказали 8-10 тыс максимум…

Звоню владельцу мойки по поводу оплаты… В общем после длительного телефонного разговора я озвучил окончательную стоимость 6 тыс. На мой взгляд, хозяину мойки это показалось дорого, говорит могу оплатить максимум 5 тыс, а судя по намёкам всё сводилось и вовсе к 3тыс.

В общем оплатил он 6 тыс…, но чувствую что в результате у него остался какой-то осадок…, да и мне как-то не очень приятно на душе в итоге(( 

Хотя если учесть все расходы на поездки, бензин, герметик, термоусадки, покупку нового паяльника (-300руб., мой пришёл в негодность посреди работы),  если учесть то, что я согласился уйти в рабочее время с основной работы ради того, чтобы побыстрее запустить его мойку — 6 тыс. это не много и ко мне претензий быть не должно!


Изменено 29 Августа 2021 пользователем Борис_мэн

ASDA-A2

AL008:Abnormal Pulse Command

Causes

The pulse command

frequency is higher than

the rated input

frequency.

AL009:Excessive Deviation of Position Command

Causes

Parameter P2-35 is set

too small

The setting of the gain

value is too small.

The torque limit is too

low.

Excessive external load

Improper setting of E-

gear ratio

AL011:Encoder Error

Causes

Wrong wiring of the

encoder

The encoder is loose

Bad connection of the

encoder

The encoder is damaged Check if the motor is damaged

AL012:Adjustment Error

Causes

The analog input contact

is incorrectly set back to

zero

The detection device is

damaged

AL013:Emergency Stop

Causes

Press the emergency

stop button

10-12

Checking Method

Use the scope to check if the input

frequency is over the rated input

frequency.

Checking Method

Check the setting value of

parameter P2-35 (The warning

condition of excessive position

deviation)

Check if the setting value is

appropriate

Check the torque limit value

Check the external load

Make sure if the proportion of P1-44

and P1-45 is appropriate.

Checking Method

Check if the wiring follows the

suggested wiring of the user

manual.

Check the drive connector of CN2

and encoder

Check if the connection between

CN2 of the drive and the encoder of

the servo motor is loose

Checking Method

Measure if the voltage of the analog

input contact is the same as the

ground voltage

Reset the power supply

Checking Method

Check if the emergency stop button

is enabled.

Chapter 10 Troubleshooting

Corrective Actions

Correctly set the input pulse

frequency.

Corrective Actions

Increase the setting value of P2-35

(The warning condition of

excessive position deviation)

Correctly adjust the gain value

Correctly adjust the torque limit

value

Reduce the external load or

evaluate the motor capacity again

Correctly setup E-gear ratio

Corrective Actions

Correct wiring

Install the encoder again

Reconnect the wiring

Change the motor

Corrective Actions

Correctly ground the analog input

contact

If the error still occurs after reset,

send the drive back to the

distributors or contact with Delta.

Corrective Actions

Activate emergency stop

Revision February, 2017

Mehobr

Почётный участник
Почётный участник
Сообщения: 162
Зарегистрирован: 15 июн 2015, 00:20
Репутация: 18
Настоящее имя: Евгений
Контактная информация:

Сервопривод Delta ASDA-B2

Уважаемые, форумчане, помогите с сервоприводом delta asda-b2.

После простоя станка и соответственно привода в 2 месяца, при включении станка неожиданно выскочила ошибка AL001.

Сняв двигатель со станка, начал проверять по мануалу возможные причины неисправности:

И так первое что я проверил на короткое замыкание на выходе привода, прозвонив провода питания. Вроде короткого замыкания и замыкания на корпус нет.

Второе: проверил на предмет неправильного подключения двигателя — все правильно тем более что привод работал нормально два месяца назад и я его не трогал с последнего успешного запуска.

Третье: неисправность IGBT — Радиатор не греется.

Четвёртое: сбросил параметры до заводских установок — не помогло убрать ошибку.

Вот, собственно и всё что я смог сделать сам.

Прошу у форумчан помощи разобраться с приводом. Или может кто возьмётся провести ремонт, за соответствующую оплату.

За ранее спасибо огромное!

Mehobr

Почётный участник
Почётный участник
Сообщения: 162
Зарегистрирован: 15 июн 2015, 00:20
Репутация: 18
Настоящее имя: Евгений
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

Mehobr » 30 мар 2020, 14:43

Да, один к сожалению такой 750Вт.
Второй 400Вт.
Как ещё можно выяснить что не исправно, серво- усилитель или двигатель?

Аватара пользователя

Serg

Мастер
Сообщения: 21923
Зарегистрирован: 17 апр 2012, 14:58
Репутация: 5180
Заслуга: c781c134843e0c1a3de9
Настоящее имя: Сергей
Откуда: Москва
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

Serg » 30 мар 2020, 15:41

Mehobr писал(а):Как ещё можно выяснить что не исправно, серво- усилитель или двигатель?

1. Сохранить все настройки в файл. Сбросить все настройки в дефолт. Если ошибка исчезла, значит проблема в настройках.
2. Отключить кабель от двигателя (вращение не включать!). Если ошибка исчезла, то проблема в двигателе.
3. Отключить кабель двигателя от драйвера (вращение не включать!). Если ошибка исчезла, то проблема в кабеле..
4. Проблема в драйвере.

Я не Христос, рыбу не раздаю, но могу научить, как сделать удочку…

Duhas

Мастер
Сообщения: 1932
Зарегистрирован: 10 окт 2015, 23:25
Репутация: 283
Настоящее имя: Андрей
Откуда: Красноярск
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

Duhas » 31 мар 2020, 02:41

можно по идее и более слабый двигатель прицепить

Аватара пользователя

Serg

Мастер
Сообщения: 21923
Зарегистрирован: 17 апр 2012, 14:58
Репутация: 5180
Заслуга: c781c134843e0c1a3de9
Настоящее имя: Сергей
Откуда: Москва
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

Serg » 31 мар 2020, 03:01

Это не имеет смысла, результат по идее будет такой: AL004. :)

Я не Христос, рыбу не раздаю, но могу научить, как сделать удочку…

Duhas

Мастер
Сообщения: 1932
Зарегистрирован: 10 окт 2015, 23:25
Репутация: 283
Настоящее имя: Андрей
Откуда: Красноярск
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

Duhas » 31 мар 2020, 04:06

я хз на счет дельты, но вроде нет проблемы слабый движок прицепить..

Mehobr

Почётный участник
Почётный участник
Сообщения: 162
Зарегистрирован: 15 июн 2015, 00:20
Репутация: 18
Настоящее имя: Евгений
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

Mehobr » 31 мар 2020, 13:59

:wik: Ну, всё, бахнул драйвер и что я сделал ни так, не понятно :cry: .
И так что я сделал сегодня:
1. Отключил силовой кабель двигателя от драйвера, кабель энкодера оставил подключенным — включил драйвер, выскочила ошибка AL013. Почитав мануал изменил параметр Р2-17 со значения 21 на значение 20. Ошибка исчезла.
2. Выключил драйвер, подключил силовой кабель от двигателя. Включаю драйвер, ошибки нет, обрадовался.
3. Решил провести по мануалу пробный пуск без нагрузки в режиме «JOG». Для этого устанавливаю параметр Р2-30 равным 1, нажимаю кнопку Set и тут бахнуло что то внутри драйвера, я чуть не оглох.
Вот и всё теперь точно нужен ремонт. У нас есть специалисты?

Mehobr

Почётный участник
Почётный участник
Сообщения: 162
Зарегистрирован: 15 июн 2015, 00:20
Репутация: 18
Настоящее имя: Евгений
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

Mehobr » 31 мар 2020, 14:23

Разобрал драйвер чтобы посмотреть что бахнуло.
На фото выделил красным, что там было теперь неизвестно.

Вложения
20200331_130344.jpg (7651 просмотр) <a class='original' href='./download/file.php?id=179325&sid=8d68b934d4886493cbac29ce8e582903&mode=view' target=_blank>Загрузить оригинал (2.24 МБ)</a>

Mehobr

Почётный участник
Почётный участник
Сообщения: 162
Зарегистрирован: 15 июн 2015, 00:20
Репутация: 18
Настоящее имя: Евгений
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

Mehobr » 02 апр 2020, 18:00

PnP писал(а):Там бал резистор.

Подскажите, какой номинал резистора? На фото не могу прочесть.

Аватара пользователя

xvovanx

Мастер
Сообщения: 3537
Зарегистрирован: 25 фев 2016, 12:27
Репутация: 860
Настоящее имя: Владимир
Откуда: Latvia
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

xvovanx » 02 апр 2020, 18:37

Mehobr писал(а):бахнуло что то внутри драйвера, я чуть не оглох.

Mehobr писал(а):Подскажите, какой номинал резистора? На фото не могу прочесть.

Резистор просто так не сгорает с оглушительным звуком, это уже следствие. Проверяйте полевик, электролиты, диоды, диодный мост, дорожки.

PnP

Опытный
Сообщения: 171
Зарегистрирован: 15 фев 2020, 22:38
Репутация: 40
Настоящее имя: Сергей
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

PnP » 02 апр 2020, 22:40

Mehobr писал(а):Подскажите, какой номинал резистора? На фото не могу прочесть.

Вы если на фото кликните то она в окне откроется, там есть справа внизу «загрузить оригинал» нажмите и откроется с большим разрешением.
Ну а так на резисторе написано R020 мне видится это наверно или 20ом или 2ома, ну и судя по размеру вата на два, может и больше.

PnP

Опытный
Сообщения: 171
Зарегистрирован: 15 фев 2020, 22:38
Репутация: 40
Настоящее имя: Сергей
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

PnP » 02 апр 2020, 22:49

xvovanx писал(а):Резистор просто так не сгорает с оглушительным звуком, это уже следствие. Проверяйте полевик, электролиты, диоды, диодный мост, дорожки.

Владимир, прав, это следствие. Вы по плате посмотрите куда от него (резистора) дорожки ведут, может он часть RC цепочки кондер прошило и на резисторе цепь замкнулась на пробитом кондере так часто бывает, вот и сгорел. Вообщем обвязку смотрите куда он шел.

PnP

Опытный
Сообщения: 171
Зарегистрирован: 15 фев 2020, 22:38
Репутация: 40
Настоящее имя: Сергей
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

PnP » 02 апр 2020, 22:51

Вообщем яндекс говорит «Чип резисторы 0.02 ом, маркировка R020, SMD»

PnP

Опытный
Сообщения: 171
Зарегистрирован: 15 фев 2020, 22:38
Репутация: 40
Настоящее имя: Сергей
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

PnP » 02 апр 2020, 22:59

Как вариант можете еще тестером на прозвонке потыркать от выводов этого резистора по ножкам разъема что с винтиками.
Может на каком и зазвенит, тогда посмотрите что у вас на этом винте прикручено, может какую проводку на станке замкнуло,
вот резистор и сдох.

aalex_b

Новичок
Сообщения: 27
Зарегистрирован: 11 мар 2016, 15:27
Репутация: 1
Настоящее имя: Александр
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

aalex_b » 13 окт 2020, 15:06

Добрый день.

В станке CTX310 c siemens840sl в качестве привода револьвера стоит частотничек Delta ASDA-A2. Суть проблемы: во время работы появляется ошибка по сверхтоку AL.001
Станок разгоняю, могу вращать револьвер, но через пару минут выскакивает ошибка. Когда даже задания нет и револьверка в режиме покоя находится, т.е. зажата.

zkxFTF

Кандидат
Сообщения: 48
Зарегистрирован: 24 окт 2019, 19:08
Репутация: 0
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

zkxFTF » 07 дек 2022, 08:46

Всем привет! Подскажите пожалуйста, для снятия ошибки 13, подаю сигнал на пин 30 5в, ошибка не снимается. Что делаю не так ?

Аватара пользователя

niksooon

Мастер
Сообщения: 2090
Зарегистрирован: 23 июн 2014, 23:18
Репутация: 1193
Откуда: Кашира
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

niksooon » 07 дек 2022, 20:17

почему 5 в на вход а не 220?

Последний раз редактировалось niksooon 07 дек 2022, 20:28, всего редактировалось 1 раз.

Сделанное правильно — красиво. Если сделанное тебе не нравится — то и работать оно будет хреново. Перевари, пересверли, выпили заново — ну, или хотя бы покрась.

rry

Опытный
Сообщения: 159
Зарегистрирован: 25 дек 2020, 12:01
Репутация: 24
Настоящее имя: Victor
Контактная информация:

Re: Сервопривод Delta ASDA-B2

Сообщение

rry » 07 дек 2022, 20:24

30 пин это DI8 ? снятие аларма на него назначено?
в А3 там надо +24В на COM pin11 и 0 на вход сигнала
А2 так-же наверное

Delta Servo Drive Alarm on ASDA B2. In this article, I guide you to clear some popular alarms on Delta servo drive ASDA B2. It is helpful when you start learning, testing and jog-run the servo motor. This post is in the tutorial about “Delta servo“, you can refer to the previous posts on 365evn.

The first time, when you working on the Delta servo drive or after you make a delta servo factory reset, some alarms appear and you can not make a jog-run or test the servo. Some alarms on Delta servo drive as alarm no AL.013, AL.014, AL.015, and AL.011. In this article, I guide you to clear the above alarm on Delta servo drive ASDA B2, you can use the method to fix the alarm on other Delta servo series such as B3, AB…

servo-motor-and-drive-delta-asda-b2
Servo motor and drive Delta asda-b2

The default functions of the Delta servo input DI6/7/8 are reverse limit/forward limit/emergency stop. For safety reasons, all contacts are normally closed contacts, so when there is no limit switch connected the above alarms on Delta servo (AL.013, AL.014, AL.015) will occur when the power is applied.

Below, I guide you to clear the delta servo drive alarm for learning or testing the delta servo. With your application, you can connect the DI6/7/8 to the limit switch and emergency stop for your safety to clear the alarm.

Clear Delta Servo Drive Alarm – AL.013

The alarm AL013 on Delta servo Drive ASDA is an alarm about “Emergency stop”. When we do not connect the Delta servo drive with an emergency stop button, the alarm will occur. We can temporarily clear the AL013 alarm by changing the parameter setting:

clear-delta-servo-drive-alarm-al013
Clear delta servo drive alarm al013
  • Go to the “P2-015” parameter
  • Change the value to “0122” and save it. The default value is “0022”.
  • Restart the delta servo drive and check again.

Clear Delta Servo Drive Alarm – AL.014, AL0.15

The alarms AL014, and AL015 on Delta servo Drive ASDA are alarmed about “Reverse limit error” and “Forward limit error”. When we do not connect the Delta servo drive with a limit switch, the alarm will occur. We can temporarily clear the delta servo drive alarm: AL014 and AL015 alarms by changing the parameter setting:

alarm-al014-al015-delta-servo-drive
Alarm AL.014, AL.015 on Delta servo drive
  • Go to the “P2-016” parameter
  • Change the value to “0123” and save it. The default value is “0023”.
  • Go to the “P2-017” parameter
  • Change the value to “0121” and save it. The default value is “0021”.
  • Restart the delta servo drive and check again.

Clear Alarm on Delta Servo Drive – AL011

The alarms AL011 on Delta servo Drive ASDA are alarmed about the “Encoder error”. When the delta servo drive can not get the signal from the encoder, the alarm will occur. If the AL011 appear the servo drive can not detect the servo motor position. To fix the delta servo drive alarm AL.011 we can follow the step below:

delta-servo-encoder-error-al011
Delta servo encoder error al011
  • Check if the encoder wiring follows the suggested wiring in the user manual.
  • Check the delta servo drive connector of CN2 and encoder. The encoder jack is might loose.
  • Bad connection of the encoder: Check the connection between CN2 of the drive and the encoder of the servo motor.
  • The encoder is damaged
  • The servo motor or servo drive is damaged.

We can check the above list, however some issues we need a technical from Delta agency or a technical with many years of experience.

Delta Servo Drive Alarm List

delta-servo-drive-alarm-list
Delta servo drive alarm list

The alarm list of the Delta servo drive you can read in the “Delta servo drive ASDA B2 user manual” (Chapter 9 – Troubleshooting). In this manual, you can find the Delta Servo Drive Alarm List and the method to fix that. You can read or download it here.

Refer to the guide video below for the detail of the steps (AL013, Al014, AL015)

How to clear AL.013, AL.014, AL.015 alarm on ASDA-B2

Clear AL.013, AL.014, and AL.015 alarms on ASDA-B2
  • Refer to more videos about “Delta servo training” on 365evn: Link
  • If you can not watch the video on youtube, please check another link in the “Video area“.

Summary

With this article, you can clear the delta servo drive alarm and test or jog run delta servo motor. Hope that it is helpful to you. Follow me on my website, Facebook, and Youtube… to get the newest content.

Bạn có thể than khảo bộ Delta servo cũ, bộ cáp lập trình đa năng cho servo, PLC, HMI… tại shop 365evn (Delta servo used and programming cable for PLC, HMI, VFD…): Link

–365EVN, refer Delta Automation–

If you find this content valuable, please rate it (click the button above), share it with your friends or invite me for a coffee by clicking the button below.

background image

Руководство по эксплуатации преобразователей VFD-M …………..………………………….…… стр. 72

Содержание: Aдрес:

Функция:

Код ошибки:
0: Ошибок не зафиксировано;
1: Превышение тока (oc);
2: Перенапряжение (ov);
3: Перегрев ПЧ (oH);
4: Перегрузка (oL);
5: Перегрузка 1 (oL1);
6: Внешняя ошибка (EF);
7: Ошибка CPU (cF1);
8: Ошибка CPU (cF3);
9: Ошибка аппаратной защиты (HPF);
10: Двукратное превышение номинального тока
при разгоне (ocA);
11: Двукратное превышение номинального тока
при замедлении (ocd);
12: Двукратное превышение номинального тока
в установившемся режиме (осn);
13: Замыкание на землю (GF);
14: Низкое напряжение (Lv);
15: Зарезервирован;
16: Отказ CPU 2 (cF2);
17: Пауза в рботе;
18: Перегрузка (oL2);
19: Авария автоматического разгона/замедления (cFA);
20: Разрешение программной защиты (codE);

Статус VFDM

00: RUN LED не светится; STOP LED светится
01: RUN LED мигает; STOP LED светится;
10: RUN LED светится; STOP LED мигает;

Bit 0-1

11: RUN LED светится; STOP LED не светится;

Bit 2

01: JOG активна
00: REV LED не светится;. FWD LED светится
01: REV LED мигает;. FWD LED светится
10: REV LED светится;. FWD LED мигает

Bit 3-4

11: REV LED светится;. FWD LED не светится

Bit 5-7

Зарезервированы.

Bit 8

1: Управление ведущей частотой по
последовательному интерфейсу.

Bit 9

1: Управление ведущей частотой аналоговым
сигналом.

Bit 10

1: Управление ПЧ от последовательного интерфейса.

Bit 11

1: Параметры заблокированы.

Bit 12

0: ПЧ остановлен, 1: ПЧ работает;

Bit 13

1: JOG команда;

2100Н

Bit 14-15 Не используется.

2102H

Заданная частота (F);

2103H

Выходная фактическая частота (H);

2104H

Выходной ток (АXXX.X);

2105H

Напряжение на шине DC U (XXX.XX);

2106H

Выходное напряжение E (XXX.XX);

Чтение

статуса

(состояния, в

том числе,

аварийного)

преобразователя

2107H

Номер шага дискретного управления скоростью;

Содержание: Aдрес:

Функция:

Чтение 2108H

Время действия PLC (сек)

Уважаемые,  форумчане, помогите с сервоприводом delta asda-b2.

После простоя станка и соответственно привода в 2 месяца, при включении станка неожиданно выскочила ошибка AL001.

Достав мануал я стал проверять возможные причины неисправности:

И так первое что я проверил на короткое замыкание на выходе привода, прозвонив провода питания. Вроде короткого замыкания и замыкания на корпус нет.

Второе: проверил на предмет неправильного подключения двигателя — все правильно тем более что привод работал нормально  два месяца назад и я его не трогал с последнего успешного запуска.

Третье: неисправность IGBT — не знаю что это. Радиатор не греется. 

Четвёртое: сбросил параметры до заводских установок — не помогло убрать ошибку.

Вот, собственно и всё что я смог сделать сам.

Прошу  у форумчан помощи разобраться с приводом. Или может кто возьмётся провести ремонт, за соответствующую оплату.

За ранее спасибо огромное!

  • Ремонт сервоприводов DELTA в Арысь
  • Ремонт сервоприводов DELTA в СЦ «РемПромЭл»
  • Настройка сервоусилителей DELTA в Арысь
  • Подключение сервопривода DELTA
  • Ошибки сервопривода DELTA
  • Коды ошибок сервопривода DELTA ASDA-AB
  • Типы сервоприводов DELTA
  • Оставить заявку на ремонт сервопривода DELTA

Ремонт сервоприводов DELTA в Арысь

Ремонт серовприводов DELTA

Ремонт сервоприводов DELTA в Арысь, одна из многих услуг предлагаемых сервисным центром «РемПромЭл». Сервопривод относится к сложной промышленной электронике и состоит из двух взаимосвязанных составляющих- это электронная и силовая часть. Подобное конструктивное исполнение значительно усложняет ремонт сервоприводов DELTA.

Сервопривода достаточно распространенное промышленное оборудование, и как все подвержены износу. В зависимости от интенсивности использования, нагрузки, среды в которой работает оборудования сервопривода выходят из строя останавливая рабочий процесс.

В целях сомнительной «экономии» некоторые пытаются провести ремонт сервоусилителя DELTA самостоятельно на территории производства. Зачастую данные действия приводят к значительному удорожанию ремонта а при самом неблагоприятном исходе могут привести к не ремонтопригодности серводрайвера.

В виду вышесказанного, настоятельно рекомендуем, не пытайтесь проводить ремонт сервоприводов DELTA своими силами, обратитесь за помощью к специалистам. Современный специализированный сервисный центр имеет в наличии весь необходимый инструмент, включая специальное диагностическое оборудование, а компетентный персонал проведет качественный ремонт сервоприводов DELTA в Арысь, дополнительно сервисные центры дают гарантию на проведенные ремонтные работы.

Ремонт сервоприводов DELTA в СЦ «РемПромЭл»

Ремонт сервоприводов DELTA

Ремонт сервоприводов DELTA в сервисном центре самое разумное и экономически выгодное решение. Грамотные специалисты со знанием дела проведут глубокую диагностику неисправного блока и последующий ремонт сервопривода DELTA в кратчайшие сроки. К написанному можно добавить то, что каждый без исключения ремонт сервопривода DELTA в СЦ «РемПромЭл» проводится с применением оригинальных запасных частей.

В 2013-ом году специалистами компании был проведен первый ремонт сервопривода DELTA положивший начало дальнейшему развитию в данном направлении. За прошедшее время были отремонтированы сотни единиц промышленного оборудования и накоплен колоссальный, бесценный опыт в ремонте сервоприводов различных производителей.

Сервисный центр «РемПромЭл» оснащен самым современным диагностическим и ремонтным оборудованием, имеются в наличии расходные материалы, а так же на складе компании богатый выбор оригинальных запасных частей, что дает возможность провести качественный ремонт сервоприводов DELTA.

Обратившись в СЦ за ремонтом сервоприводов вы получите:

  • Глубокую диагностику с выявлением неисправного компонента;
  • Чистку неисправного блока;
  • Ремонт сервопривода DELTA в кратчайшие сроки;
  • Настройка сервоусилителя;
  • Проверку отремонтированного блока на специальном стенде в условиях максимально приближенных к реальным;
  • Видео проверки отремонтированного серводрайвера.

Отдельное внимание мы уделяем качеству проведения ремонта и даем гарантию на ремонт сервоприводов DELTA, а так же на замененные в процессе ремонта запасные части и расходные материалы 6 месяцев.

Настройка сервоусилителей DELTA в Арысь

Настройка сервоприводов DELTA

Настройка сервоприводов (сервоусилителей) — это заключительный этап ремонта и в тоже время очень важный. Для правильной работы восстановленного блока просто необходимо провести грамотное программирование сервоусилителя. Ремонт и дальнейшую настройку сервоприводов выполняют разные специалисты, так как подобная работа довольно сложная и имеет свою специфику.

Настройка сервоусилителей или как еще называют программирование сервоприводов DELTA, неотъемлемая часть процесса реанимирования, ввиду того, что ремонт силовой части это только половина мероприятий направленных на восстановление работоспособности сервоприводов.

В некоторых случаях возникает необходимость провести программирование сервоусилителя без его ремонта. Причин по которым может возникнуть подобная необходимость масса.

Настройка сервоуслилтелей DELTA в Арысь может быть и отдельной услугой предоставляемой сервисным центром «РемПромЭл». Инженеры компании проведут необходимую настройку сервоприводов не только на территории сервисного центра, при необходимости можно заказать услугу выезда специалиста на территорию заказчика (по предварительной договоренности).

От качественной настройки сервоусилителя зависит правильная и безаварийная работа связки сервопривода и серводвигателя, а для этого требуется не много, просто программирование сервопривода DELTA должен проводить компетентный персонал с богатым опытом по настройке сервоуслилтелей.

Подключение сервопривода DELTA

Подключение сервопривода DELTA

Подключение сервопривода DELTA к оборудованию заказчика это еще одна услуга предоставляемая нашей компанией.

При необходимости специалист центра выполнит подключение сервопривода DELTA с выездом на территорию заказчика.

В некоторых случаях на производстве может быть дефицит квалифицированны кадров которые могли бы произвести качественное подключение сервопривода, именно по этому мы предлагаем услуги нашего сервисного центра.

Свяжитесь с нашими менеджерами, закажите выезд специалиста, и подключением сервопривода DELTA займется инженер сервисного центра. В случае заказа на подключение сервопривода DELTA силами наших специалистов вы получаете гарантию качества и работоспособности вашего оборудования.

Доверяя работу по подключению сервопривода DELTA профессионалам, вы избавляетесь от головной боли и гарантированно получаете работающее оборудование в кратчайшие сроки за разумную цену.

Схемы подключений сервоприводов DELTA

Ошибки сервопривода DELTA

Ремонт сервопривода DELTA

Многие сервопривода данного производителя, за редким исключением оснащен информационной панелью с помощью которой проходит процесс программирования сервоприводов, а так же на ней в случае нештатной ситуации отображается код ошибки которая привела к остановке оборудования.

У каждого производителя разные коды ошибок у кого то это могут быть цифровые обозначения у кого то буквенные, но вся прелесть заключается в том, что открыв документацию и расшифровав код ошибки сервопривода мы с большой долей вероятности можем исправить эту ошибку на месте, сбросить ее на сервоприводе и запустить оборудование заново.

К сожалению не все ошибки сервоприводов можно исправить и сбросить самостоятельно, в некоторых случаях придется обращаться к специалистам сервисного центра.

Самые распространенные ошибки сервоприводов:

  • Превышение тока;
  • Перенапряжение или недостаточное напряжение;
  • Перегрузка;
  • Ошибка сигнала энкодера;
  • Превышение температуры IGBT-модуля ;
  • Ошибка связи;
  • Обрыв фазы питания;
  • Короткое замыкание.

Это не полный список распространенных ошибок сервоприводов которые можно сбросить самостоятельно без обращения к специалистам.

Коды ошибок сервопривода DELTA ASDA-AB

Ошибка Причина Устранение
ALE01
  1. Короткое замыкание на выходе привода (клеммы U, V, W).
  2. Неправильное подключение двигателя.
  3. Неисправность IGBT.
  4. Некорректно установлены параметры.
  • Ошибка команд управления
  1. Проверьте наличие замыкания на выходе привода или замыкания проводов на корпус.
  2. Выполните рекомендации руководства по правильному подключению двигателя.
  3. Обратитесь в сервисный центр или к поставщику.
  4. Произведите сброс параметров и при необходимости запрограммируйте снова.
  • Обеспечьте стабильность сигнала задания.
  • Активируйте функцию фильтр.
ALE02
  1. Напряжение силовой части превысило максимально допустимое значение.
  2. Превышение входного напряжения питания.
  1. Используйте соответствующее питание или стабилизатор напряжения.
  2. Используйте соответствующее питание или стабилизатор напряжения.
ALE03
  1. Напряжение силовой части снизилось ниже допустимого значения.
  2. Отсутствует питание силовой части схемы.
  3. Неисправность сетевого питания.
  1. Подключите правильно кабель питания.
  2. Проверьте исправность выключателя питания.
  3. Используйте соответствующее питание или стабилизатор напряжения.
ALE04 Неисправность энкодера двигателя.
  • Замените двигатель.
  • Заново подключите энкодер в соответствии со схемой
ALE05

Не подключен тормозной резистор.

Неисправен тормозной транзистор.

Некорректно установлены параметры.

  1. Подключите тормозной резистор заново.
  2. Возвратите привод поставщику.
  3. Установите параметры соответствующие тормозному резистору.
ALE06
  1. Нагрузка превышает номинальную для привода в процессе работы.
  2. Некорректно установлены параметры управления.
  3. Неправильное подключение двигателя или энкодера.
  1. Увеличьте мощность привода или уменьшите нагрузку.
  2. Проведите настройку системы управления.
  3. Увеличьте время разгона / замедления.
  4. Произведите правильное подключение.
ALE07
  1. Нестабилен сигнал задания скорости.
  2. Некорректная установка параметров.
  1. 1. Обеспечьте стабильность сигнала задания.
    2.Активируйте функцию фильтра (параметры Р1-06 ÷ Р1-08)
  2. Установите необходимое значение ограничения скорости (Р2-34).
ALE08 Частота входного сигнала задания выше допустимой величины. Установите правильное значение частоты входного сигнала.
ALE09
  1. Слишком малое значение параметра для отклонения.
  2. Малое значение коэффициента усиления.
  3. Слишком низкое ограничение момента.
  4. Возможная перегрузка.
  1. Увеличьте значение параметра допустимого отклонения (Параметр Р2-35).
  2. Установите необходимое значение коэффициента.
  3. Установите необходимое значение ограничение момента.
  4. Уменьшите внешнюю нагрузку.
    Замените привод на более мощный.
ALE10 Ошибка работы сторожевого таймера. Если после сброса напряжения питания ошибка повторяется обратитесь в сервисный центр или к поставщику.
ALE11
  1. Неправильное подключение энкодера.
  2. Энкодер не подключен.
  3. Неисправность кабеля энкодера.
  4. Неисправен энкодер.
  1. Подключите энкодер правильно.
  2. Подключите разъём энкодера.
  3. Подключите исправный кабель.
  4. Замените двигатель.
ALE12 Смещение входного сигнала превышает допустимую величину. Если ошибка не устраняется, обратитесь в сервисный центр или к поставщику.
ALE13 Включен выключатель аварийного останова. Отключите аварийный выключатель.
ALE14
  1. Включен выключатель ограничения «назад».
  2. Нестабильность сервосистемы.
  1. Отключите выключатель ограничения.
  2. Измените параметры и произведите настройку системы.
ALE15
  1. Включен выключатель ограничения «вперед».
  2. Нестабильность сервосистемы.

Отключите выключатель ограничения.

Измените параметры и произведите настройку системы.

В таблице выше представлены далеко не все коды ошибок отображаемые на дисплей сервопривода DELTA ASDA-AB. Все вожможные коды ошибок вы можете посмотреть либо скачать в удобном формате — PDF.

Все возможные ошибки сервопривода DELTA ASDA-AB — Скачать в формате PDF

Типы сервоприводов DELTA

Сервопривод Тип сервопривода

DELTA

ASD-B3-0721-E; ASD-B2-2023-B; ASD-B2-3023-B; ASD-A2-5523-M; ASD-A2-3023-M; ASD-A2-4523-M; ASDA-A2-1F43-U; ASDA-A2-1F43-M; ASD-A2-1B23-M; ASD-A2R-1B43-U; ASD-A2R-1B43-M; ASD-A2-7543-U; ASD-A2-7543-M; ASD-A2-5543-U; ASD-A2-5543-M; ASD-A2-4543-U; ASD-A2-4543-M; ASD-A2-3043-U; ASD-A2-3043-M; ASD-M-1521-R; ASD-A2-1543-U ASDA-A2; ASD-A2-1543-M; ASD-A2-1521-U; ASD-A2-1521-M; ASD-A2-1521-L; ASD-A2R-1521-M; ASD-A2R-1521-L; ASD-A0111-AB; ASD-A0121-AB; ASD-A0211-AB; ASD-A0221-AB; ASD-A0411-AB; ASD-A0421-AB; ASD-A0721-AB; ASD-A1021-AB; ASD-A1521-AB; ASD-A2023-AB

Указанные в таблице типы сервоприводов DELTA это далеко не все сервопривода данного производителя, ремонт которых производит наш сервисный центр. Мы предлагаем качественный ремонт сервоприводов в Арысь выпущенных не только под брендом DELTA инженеры центра выполнят ремонт сервоприводов абсолютно любых производителей и года выпуска.

Оставить заявку на ремонт сервопривода DELTA

Ремонт сервоприводов DELTA

Вы заинтересованы в качественном ремонте дорогостоящего промышленного оборудования силами специалистов нашего сервисного центра, Вы сделали правильный выбор, мы приложим максимум усилий для скорейшего восстановления вышедшего из строя серводрайвера, что позволит Вам максимально сократить простой оборудования и сэкономить значительную сумму.

У вас есть проблемы с сервоприводом? Вам нужен срочный ремонт сервопривода DELTA или других серий? Оставьте заявку на ремонт сервопривода DELTA в Арысь воспользовавшись одноименной кнопкой на сайте либо обратитесь к нашим менеджерам. Связаться с ними можно несколькими способами:

contact

  • Заказав обратный звонок (кнопка в правом верхнем углу сайта)
  • Посредством чата (кнопка расположена с левой стороны сайта)
  • Позвонив по номеру телефона: +7(927)610-78-70; +7(848)255-80-30
  • Написав на электронную почту: Адрес электронной почты защищен от спам-ботов. Для просмотра адреса в вашем браузере должен быть включен Javascript.
  • Перейти в начало статьи

Понравилась статья? Поделить с друзьями:

Не пропустите эти материалы по теме:

  • Яндекс еда ошибка привязки карты
  • Al 60 ошибка на пеканиске
  • Alert irruption ошибка терминала ingenico ict220
  • Ald ошибка 283
  • Al 31 данфосс al31 ошибка

  • 0 0 голоса
    Рейтинг статьи
    Подписаться
    Уведомить о
    guest

    0 комментариев
    Старые
    Новые Популярные
    Межтекстовые Отзывы
    Посмотреть все комментарии